Room Fan Coil Unit - Performance Data


Two-Pipe UnitFour-Pipe UnitTwo-Pipe Unit With Electric Heat

Cooling Capacities for
2 Pipe Heating / Cooling
2 Pipe Cooling Only
4 Pipe Heating / Cooling
Entering Air Dry Bulb 80°F    Entering Air Wet Bulb 67°F    6 F.P.S. Vel.
Average
50°F
48°F
46°F
Water Temp.
Unit Size-Nominal CFM
Total
Sensible
Total
Sensible
Total
Sensible
Heat
Heat
Heat
Heat
Heat
Heat
200
5930
4120
6500
4550
7090
4970
300
8570
5980
9520
6660
10380
7200
300X
10040
7340
11050
7660
11850
8090
400
12240
9450
13600
10480
14730
11420
500
13190
10320
14670
11520
16100
12580
600
16960
13160
18840
14620
20580
15820
800
23360
17380
25960
19310
28300
21100
 
Entering Air Dry Bulb 78°F    Entering Air Wet Bulb 65°F    6 F.P.S. Vel.
Average
50°F
48°F
46°F
Water Temp.
Unit Size-Nominal CFM
Total
Sensible
Total
Sensible
Total
Sensible
Heat
Heat
Heat
Heat
Heat
Heat
200
5510
3890
6130
4310
6740
4740
300
8100
5670
9100
6250
10010
6870
300X
9530
7010
10400
7430
11360
7990
400
11600
8950
12820
9910
14100
10900
500
12480
9800
13810
10880
15190
11960
600
15800
12410
17820
13780
19650
15150
800
22100
16500
24500
18250
26900
20100
 
Entering Air Dry Bulb 75°F    Entering Air Wet Bulb 63°F    6 F.P.S. Vel.
Average
50°F
48°F
46°F
Water Temp.
Unit Size-Nominal CFM
Total
Sensible
Total
Sensible
Total
Sensible
Heat
Heat
Heat
Heat
Heat
Heat
200
4600
3180
5040
3520
5500
3840
300
6650
4140
7520
5100
8210
5560
300X
7960
6460
8740
6780
9520
7110
400
9510
6950
10550
8110
11600
8840
500
10250
7600
11350
8860
12400
9170
600
13150
10450
14600
11100
15950
12200
800
18200
13500
20800
14910
21700
16300
 
Entering Air Dry Bulb 95°F    Entering Air Wet Bulb 78°F    6 F.P.S. Vel.
Average
50°F
48°F
46°F
Water Temp.
Unit Size-Nominal CFM
Total
Sensible
Total
Sensible
Total
Sensible
Heat
Heat
Heat
Heat
Heat
Heat
200
11500
6100
12180
6450
14200
7100
300
17400
9250
18320
9710
20150
10700
300X
19540
10920
20450
11250
21970
11800
400
23500
12500
24750
13600
27220
14960
500
29300
15600
30900
16400
34000
18100
600
35200
18750
37070
19620
40740
21560
800
45300
23200
47700
25300
52470
27800
 
Entering Air Dry Bulb 87.5°F    Entering Air Wet Bulb 72.5°F    6 F.P.S. Vel.
Average
50°F
48°F
46°F
Water Temp.
Unit Size-Nominal CFM
Total
Sensible
Total
Sensible
Total
Sensible
Heat
Heat
Heat
Heat
Heat
Heat
200
8280
5140
8800
5460
9610
5960
300
12500
7740
13280
8150
14100
8900
300X
13400
8500
14100
8800
15200
9200
400
16600
10280
17600
10900
19200
11890
500
20320
12600
22000
13610
24100
14850
600
24200
15000
25710
15900
28200
17460
800
34100
21800
35200
21910
38400
23800
 
Entering Air Dry Bulb 83.8°F    Entering Air Wet Bulb 68.8°F    6 F.P.S. Vel.
Average
50°F
48°F
46°F
Water Temp.
Unit Size-Nominal CFM
Total
Sensible
Total
Sensible
Total
Sensible
Heat
Heat
Heat
Heat
Heat
Heat
200
6460
4910
7110
5050
7760
5510
300
9700
7370
10650
7670
11650
8370
300X
10600
7700
11500
8100
12400
8500
400
12980
9850
14200
10400
15500
11380
500
16100
12200
17750
12780
19400
13950
600
19450
14750
20300
14600
22800
15910
800
25800
19600
28400
20100
29980
21980

    Top of Page  •  Site Map  •  ©2006, The Whalen Company