50/50 Four Pipe System


Features and Benefits  •  Advantages for the Building Owner
Advantages for the Contactor



How It Works


Outdoor Air - 20°F and Below
Pump P1 and P2 are operating in parallel. P3 is on standby and remains off.


Outdoor Air - 20°F and Below 40°F
System moves into a partial heating load requirement. The 50/50 system allows for P2 to be shut down by an outdoor reset, leaving the system at 50% flow capacity and operating at a 50% pumping reduction. Valves are positioned by the reset schedule or a relay connected to P2.


Outdoor Air - 40°F and Below 60°F
Here is the most striking cost difference between a 50/50 design and a conventional 4-pipe system. Rather that 100% of the chilled and hot water flow being circuited by two pumps rated for 100% of their respective flows, the 50/50 system efficiently delivers 4-pipe capacity with half of the pumping requirement. The unnecessary full flow requirement during a marginal day is eliminated. The chiller is brought on line by outdoor reset. Valves are also positioned by the outdoor reset schedule or a delay connected P2.


Outdoor Air - 60°F to 80°F
When heating is no longer required, the boiler is shut down along with P1. Since only a partial cooling load is required, P2 circulates 50% of the total flow. Valves are positioned by the outdoor reset schedule or a relay connected to the pumps.


Outdoor Air - 80°F and Above
Design day cooling allows for both P1 and P2 to be operating in parallel delivering 100% of the chilled water flow. Valves are positioned by the outdoor reset schedule or a relay connected to the pumps.

The 50/50 system allows design day operating costs to be incurred only when necessary. By using half of the normal main size, with a double Riser Heat Exchanger in each unit, the 50/50 system delivers only the load required for each season, substantial reducing installation and operating costs.

Remember:
The pumps on a 50/50 system are up to 50% smaller than those found on a conventional 4-pipe system.

Up to 85% of the time a fan coil unit is operating at less than full capacity. The 50/50 system allows you to realize significant operational savings during this time.



Top of Page  •  Site Map  •  ©2006, The Whalen Company