| Heat
Only Unit |
| Average
Water Temp (F°) |
All
Capacities in MBH |
| W201 |
W301 |
W401 |
W501 |
W601 |
W801 |
| 110 |
6.5 |
10.0 |
11.2 |
13.5 |
15.8 |
20.5 |
| 120 |
8.2 |
12.5 |
14.0 |
16.5 |
19.8 |
25.5 |
| 130 |
9.7 |
15.0 |
16.8 |
19.5 |
23.5 |
30.5 |
| 140 |
11.5 |
17.5 |
19.2 |
23.0 |
27.2 |
35.5 |
Notes:
1) Recommended Design Water Temperature Range is between 80°F
and 140°F.
2) If entering water temperature exceeds 140°F, remote mount
thermostats are recommended.
3) For optimum comfort, an indoor/outdoor reset schedule of hot
water temperature is recommended.
4) Calculated GPM per riser is based on a 20°F temperature
drop.
5) Water velocity in riser should be between 3 and 8 feet per
second.
Top of Page >
|