Home
Products
Market Applications
Technical Data
Library
Company
Contact Us
Back To Performance Data Main >
50/50 Four Pipe System
Entering Air Dry Bulb 80°F
Entering Air Wet Bulb 67° 6 F.P.S. Vel.
Average
Water Temp.
50°F
48°F
46°F
Model
No.
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
W3022
10081
7004
11050
7735
12053
8449
W4022
11860
8240
13000
9100
14180
9940
W5022
14500
10100
16020
11210
17470
12170
W6022
17140
11960
19040
13320
20760
14400
W8022
24480
18900
27200
20960
29460
22840
W10022
26380
20640
29340
23040
32200
25160
'
Entering Air Dry Bulb 78°F
Entering Air Wet Bulb 65°F
6 F.P.S. Vel.
Average
Water Temp.
50°F
48°F
46°F
Model
No.
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
W3022
9377
6673
10721
7737
11458
8058
W4022
11020
7780
12260
8620
13480
9480
W5022
13610
9560
15230
10560
16750
11610
W6022
16200
11340
18200
12500
20020
13740
W8022
23200
17900
25640
19820
28200
21800
W10022
24960
19600
27620
21760
30380
23920
Entering Air Dry Bulb 75°F
Entering Air Wet Bulb 63°F
6 F.P.S. Vel.
Average
Water Temp.
50°F
48°F
46°F
Model
No.
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
Total
Heat
Sensible
Heat
W3022
7820
5406
8568
5984
9350
6528
W4022
9200
6360
10080
7040
11000
7680
W5022
11250
7320
12560
8620
13710
9400
W6022
13300
8280
15040
10200
16420
11120
W8022
19020
13900
21100
16220
23200
17680
W10022
20500
15200
22700
17720
24300
18340
Top of Page >
©2010 The Whalen Company