| Cooling
Capacities for 2 Pipe Heating / Cooling, 2 Pipe Cooling Only, 4 Pipe Heating / Cooling |
| Entering
Air Dry Bulb 80°F Entering
Air Wet Bulb 67°F 6
F.P.S. Vel. |
Average
Water Temp. |
50°F |
48°F |
46°F |
| Unit
Size-Nominal CFM |
Total
Heat |
Sensible
Heat |
Total
Heat |
Sensible
Heat |
Total
Heat |
Sensible
Heat |
| 200 |
5930 |
4120 |
6500 |
4550 |
7090 |
4970 |
| 300 |
8570 |
5980 |
9520 |
6660 |
10380 |
7200 |
| 300X |
10040 |
7340 |
11050 |
7660 |
11850 |
8090 |
| 400 |
12240 |
9450 |
13600 |
10480 |
14730 |
11420 |
| 500 |
13190 |
10320 |
14670 |
11520 |
16100 |
12580 |
| 600 |
16960 |
13160 |
18840 |
14620 |
20580 |
15820 |
| 800 |
23360 |
17380 |
25960 |
19310 |
28300 |
21100 |
| Entering
Air Dry Bulb 78°F Entering
Air Wet Bulb 65°F 6
F.P.S. Vel. |
Average
Water Temp. |
50°F |
48°F |
46°F |
| Unit
Size-Nominal CFM |
Total
Heat |
Sensible
Heat |
Total
Heat |
Sensible
Heat |
Total
Heat |
Sensible
Heat |
| 200 |
5510 |
3890 |
6130 |
4310 |
6740 |
4740 |
| 300 |
8100 |
5670 |
9100 |
6250 |
10010 |
6870 |
| 300X |
9530 |
7010 |
10400 |
7430 |
11360 |
7990 |
| 400 |
11600 |
8950 |
12820 |
9910 |
14100 |
10900 |
| 500 |
12480 |
9800 |
13810 |
10880 |
15190 |
11960 |
| 600 |
15800 |
12410 |
17820 |
13780 |
19650 |
15150 |
| 800 |
22100 |
16500 |
24500 |
18250 |
26900 |
20100 |
| Entering
Air Dry Bulb 75°F Entering
Air Wet Bulb 63°F 6
F.P.S. Vel. |
Average
Water Temp. |
50°F |
48°F |
46°F |
| Unit
Size-Nominal CFM |
Total
Heat |
Sensible
Heat |
Total
Heat |
Sensible
Heat |
Total
Heat |
Sensible
Heat |
| 200 |
4600 |
3180 |
5040 |
3520 |
5500 |
3840 |
| 300 |
6650 |
4140 |
7520 |
5100 |
8210 |
5560 |
| 300X |
7960 |
6460 |
8740 |
6780 |
9520 |
7110 |
| 400 |
9510 |
6950 |
10550 |
8110 |
11600 |
8840 |
| 500 |
10250 |
7600 |
11350 |
8860 |
12400 |
9170 |
| 600 |
13150 |
10450 |
14600 |
11100 |
15950 |
12200 |
| 800 |
18200 |
13500 |
20800 |
14910 |
21700 |
16300 |
Top of Page >
|